Specifications

Minimum Cold Temperature Supply 5C
Maximum Cold Temperature Supply 30C
Minimum Hot Temperature Supply 55C
Maximum Hot Temperature Supply 90C
Minimum Thermostatic Temperature 35C
Maximum Thermostatic Temperature 48
Maximum Flow Rate (L/min@200kPa pressure loss) 39
Minimum Flow Rate for Stable Outlet Temperature (L/min) 4
Minimum Flow Rate (L/min) 2
Maximum Flow Rate (L/min) 45
Inlet Connection 20mm(Nom.) OD Copper tails
Outlet Connection 20mm(Nom.) OD Copper tails
  • Lift Lever Thermal Flush activation incorporated within the headworks for faster, safer, more efficient thermal disinfection capability
  • Manufactured from Lead Free brass components - including pipe fittings
  • Scald and thermal shock protection with rapid thermal shut-off should either the cold or hot water supply fail
  • Highly responsive temperature control, maintaining outlet temperature within +/- 2?C under changing inlet temperature and pressure conditions
  • Delivers high flow at low pressure loss
  • Supplied complete with isolating valves, non-return valves and dual stage strainers incorporating temperature/ pressure test ports
  • Pipework is designed to reduce flow restrictions and minimise bacterial capture points to reduce the risk of bacterial contamination
  • Flexible installation - can be upside down or sideways, inlet and outlet connections may be rotated to suit pipework design
  • A range of suitable Stainless Steel lids are available for this model:
  • ATMSHL-350 - Hinged Lid with wall flange
  • ATMSXP-350 - Exposed Lid
  • ATMSSEC-350 - Secure/Heavy Duty Lid
  • Standards licensed to AS4032.1 - Thermostatic Mixing Valves
  • NSW Health Approved

Approval Information

WaterMark Licence WMKA25301

Warranty

Spare Parts